Item Code: 4-10KVA-1-PH
| Capacity | 4kva , 5kva, 6kva, 7. 5kva & 10kva | | topology | double conversion online | | input: | | voltage range | 170vac to 270vac | | frequency range | 45hz to 55hz | | power factor | 0. 8 lag. 0. 9* | | battery: | 120, 144, 180vdc | | battery type | smf, tubular, automotive | | charger type | cvcc | | charging current | 10% normal, upto 25%* | | inverter: | | voltage | 220/230/240vac or 110vac /120vac* | | tolerance | + / - 1% | | transient recovery | with in 20msec to 100% | | waveform | sinusoidal | | inverter type | pwm – igbt ( insulated gate bipolar transistor) | | protection: | | fuses | for input, battery, output & for inverter devices | | electronic trip | for output low/high voltage, over load, short circuit, dc high voltage | | overall system: | | efficiency | >90% | | bypass | manual, optional static bypass | | meter | lcd with selection | | temperature | 0 to 40’c | | humidity | 95% non condensing | | noise level | 55db at 1 meter | | dimensions in mm. Wxlxh | 350x660x600 & 400x800x805 | | type of cooling | fan. forced air cooling | | color | broken white, siemens gray | | | | indications & alarm | mains on, inv on, battery low, trip buzzer for battery low & trip | * Optional not standard parameter
|